Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T01CM02749
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/04/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 07/18/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/18/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | E1 1) The fault current parameters are incorrect. The length to the service is approximately 160'. The fault current is approximately 15.4kA. 2) The existing flag illumination does not appear to conform to C.O.T. Light Ordinance 8210. Clarify the fixture type, wattage and mounting orientation. 3) Provide placards identifying the function of the service disconnect. 99NEC 230-70(b). 4) Provide a grounding electrode system for the 25kVA transformer. 99NEC 250-30 5) Provide a placard identifying the purpose of the generator receptacle in order to avoid confusion regarding its function. 6) The "Equipment Power & Telco & Coax Plan" does not accurately reflect the service design. E2 1) Detail 2/E2 and the ground rod description in the symbol list on page E3 require a 10' ground rod however detail 1/E2 specifies an 8' rod. 2) Detail 4/E2 appears incorrect. The plan indicates there will be 2 sets of 2.5" C 3-4/0 XHHW, 1-#2 ground. See page E1. |
| 07/19/2001 | PHIL SEADER | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/25/2001 | SREEVES | PLANNING-CITY HALL | REVIEW | Completed | |
| 07/25/2001 | JAY HOGAN | OPERATIONS | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/26/2001 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |