Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T01CM02641
Parcel: 13314227B

Address:
1400 N WILMOT RD

Review Status: Completed

Review Details: SITE

Permit Number - T01CM02641
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2001 DOUG WILLIAMS ENGINEERING REVIEW Denied See comments on Site Review Record - Full Code Review required - Temporary Revocable Easement (TRE) required for parking in right of way - depict onsite refuse provisions as existing or proposed, clarify 15' easement type, include 5' of the 10' elec. easement on east property line, correct the far side SVT (Wilmot Rd.), refer to sheet C1 for details or include basin volume capacity, 100-yr water surface elev., 5-yr ret. volume provided, exiting and entering Q100's, and a note or depiction of containment of the Q100 (regulatory flow) within the channel.
10/31/2001 DOUG WILLIAMS SANITATION REVIEW Denied
10/31/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Denied
11/09/2001 DAN CASTRO ZONING REVIEW Denied COMMENTS: Provide a response letter with the next site plan submittal that states how all the Zoning Review Section comments were addressed. CODE SECTION/ DEVELOPMENT STANDARD

1. Since the proposed parking structure results in a greater than 25% expansion of the vehicular use area, the following comments are based on full code compliance review of the entire site.

2. Please clarify relationship of existing need office building to hospital. If the two uses are separate this site has a mixed use. Regardless, the GFA of office building must be included in all calculations on sheet CO.3 and use must be revised if required.

3. Label on the site plan all existing and proposed buildings and structures, including size, height, overhangs, canopies, and use. D.S. 2-02.2.1.A.6

4. a) Provide vehicle parking calculation which includes the number of parking spaces required and provided.
b) Provide a typical parking space detail for both standard and handicap parking spaces.
c) Fully dimension carports. Refer to D.S. 3-05.2.2.B.2 for setback requirements.
d) Fully dimension angles parking spaces.
e) Parking is not permitted in right-of-way without Temporary Revocable Easement (TRE). Parking with TRE in right-of-way must be excess parking.
D.S. 2-02.2.1.A.8; D.S. 2-02.2.2.A.4; L.U.C. 3.3.4
D.S. 3-05.2.2.B.2

5. a) The number and type of bicycle parking spaces required may not be verified for compliance until the vehicle parking calculation is provided.
b) Provide a fully dimensioned bicycle parking space detail. Refer to D.S. 2-09 for design criteria.
D.S. 2-02.2.1.A.9; D.S. 2-02.2.2.A.4; L.U.C. 3.3.4; D.S. 2-09

6. Label and dimension existing and future sight visibility triangles. Refer to D.S. 3-01.5.1 for criteria.
D.S. 2-02.2.1.A.10; D.S. 3-01.5.1

7. Dimension all PAAL widths or add typical. All PAAL's which are one-way (i.e. east of last addition) must be detailed.
D.S. 2-02.2.1.A.11

8. a) Demonstrate continuous on-site pedestrian circulation on site plan. On-site pedestrian circulation system must connect to Wilmot Road right-of-way.
b) Dimension the width of the pedestrian circulation system.
D.S. 2-02.2.1.A.12; D.S. 2-08

9. Provide the type, size, and height of existing and proposed free standing signage and outdoor lighting.
D.S. 2-02.2.1.A.13; D.S. 2-02.2.1.A.25

10. a) Label and dimension location of all loading spaces on the site plan.
b) Provide the size of the loading spaces required under the loading space calculation on sheet CO.3.
c) Label on-site zoning boundaries.
D.S. 2-02.2.1.A.14; L.U.C. 3.4.5.4

11. If applicable, all existing or proposed easements must be shown on the plan including width, type, and recording docket and page reference.
D.S. 2-02.2.1.A.20

12. Label and dimension future curb along Wilmot Road. Per the Major Streets and Routes Plan, future curb for a 150 foot right-of-way is located 12 feet from future right-of-way line.
D.S. 2-02.2.1.A.21

13. a) Label adjacent zoning classification to the north of the subject property.
b) Revise zoning classification south of the subject property from "C-1P" to "C-1".
D.S. 2-02.2.1.A.28

14. List the floor area for each building.
D.S. 2-02.2.2.A.2

15. List the percentage of vehicular use area expansion.
D.S. 2-02.2.2.A.6

16. Are "future additions" to hospital under this permit. If so, calculations must reflect "future additions". If "future additions" will not be under this permit please remove all references to future additions, or indicate that a separate permit is required.

17. All requested changes must be made to the site and landscape plans. D.S. 2-07.2.1.A
11/19/2001 JOE LINVILLE NPPO REVIEW Denied An application for exception has been received and is approvable for the proposed parking structure. Additional expansion areas on the site are also subject to the provisions of LUC 3.8. Submit plans for native plant preservation for additional areas as necessary.
11/19/2001 JOE LINVILLE LANDSCAPE REVIEW Denied Revise the landscape plan in accordance with the Zoning Review and Engineering Section Comments.

Based on the expansion proposed, the provisions of LUC 3.7 apply to the entire site. Prepare a landscape plan that shows the entire site including all required calculations and screening information per DS 2-07. Include adjacent uses and zones to expedite review of any exceptions requested.

The plans for this permit application should only show development currently proposed. Clarify areas of expansion on the landscape plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/26/2001 TAMI ACHONG OUT TO CUSTOMER Completed