Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T01CM02515
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/31/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1) The high phase on panel PA is 33.3 amps. In light of the fact A phase is 8 times larger than the other 2 phases it should be utilized to determine the panel load. Not addressed. 2) It is not clear where in the building this work takes place. Provide a location plan which includes the building floor plan and the location of the work within the building. Not addressed 3) The design indicates #8 conductors paralleling between 2 disconnects and then both the receptacles and the AC originate from 1 of the 2 disconnects. Clarify your intent and provide a design consistent with the panel schedule. OK 4) Provide revised circuitry plans showing the changes in the circuit numbers for the loads moved from panel PA to panel P. Not addressed 5) The ** below panel P indicates a 40 amp circuit breaker should be used. A 50 amp breaker is required and is installed to serve panel PA. Please correct. Not addressed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/03/2002 | VFLORES1 | OUT TO CUSTOMER | Completed |