Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T01CM02515
Parcel: Unknown

Address:
4902 E PIMA ST

Review Status: Completed

Review Details: REVISION

Permit Number - T01CM02515
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied 1) The high phase on panel PA is 33.3 amps. In light of the fact A phase is 8 times larger than the other 2 phases it should be utilized to determine the panel load.
2) It is not clear where in the building this work takes place. Provide a location plan which includes the building floor plan and the location of the work within the building.
3) The design indicates #8 conductors paralleling between 2 disconnects and then both the receptacles and the AC originate from 1 of the 2 disconnects. Clarify your intent and provide a design consistent with the panel schedule.
4) Provide revised circuitry plans showing the changes in the circuit numbers for the loads moved from panel PA to panel P.
5) The ** below panel P indicates a 40 amp circuit breaker should be used. A 50 amp breaker is required and is installed to serve panel PA. Please correct.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/31/2002 MONICA VALDEZ OUT TO CUSTOMER Completed