Permit Number: T01CM02515
Parcel: Unknown

Address:
4902 E PIMA ST

Review Status: Completed

Review Details: SITE

Permit Number - T01CM02515
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2001 PATRICIA GEHLEN ZONING REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES DEPARTMENT
ZONING REVIEW SECTION

DATE: October 31, 2001
ACTIVITY NUMBER: T01CM02515
PROJECT NAME: Fire Station No. 7 Apparatus Bay Addition
PROJECT ADDRESS: 4902 East Pima Street
PROJECT REVIEWER: Patricia Gehlen

The following items must be revised on or added to the site plan. Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed:

1) A copy of the recorded affirmation with attached legal descriptions must be provided. The copies provided with this submittal have not been recorded . The recordation information added to sheet A1.0 under the legal description is not the recordation information for the affirmation. Revise as required, (DS 2-02.2.1.A.2),
2) Revise the vehicle parking calculations shown on the site plan to be based on new floor area of 1121 square feet (DS 2-02.2.2.A.4, LUC 3.3.4),
3) The last approved site plan shows a back up spur in the parking lot west of the addition which must be maintained (DS 2-02.2.1.A.8, 9, & 11),
4) The existing and future half rights-of-way for Pima Street and the existing and future sight visibility triangles for the new ingress/egress location must be added to the site plan (DS 2-02.2.1.A.10, 19, and 21),
5) The lot area minimum (20,000 square feet) must be added to the site plan general notes (DS 2-02.2.2.A.1 & 3, LUC 3.2.9 & 3.2.11),
6) Dimension the setback to the new addition from the back of future curb along Pima Street (DS 2-02.2.1.A.7),
7) Resubmittal of these plans are not required. Call 791-5608 to set an appointment with the reviewer for an over-the-counter approval.
11/06/2001 MATT FLICK ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/21/2001 TAMI ACHONG OUT TO CUSTOMER Completed