Permit Number: T01CM02515
Parcel: Unknown

Address:
4902 E PIMA ST

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T01CM02515
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/29/2001 JIM EGAN FIRE REVIEW Approved
05/29/2001 MARK TITUS WATER REVIEW Approved
06/20/2001 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approv-Cond
06/22/2001 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
06/25/2001 GERRY KOZIOL WWM REVIEW Approved
06/25/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Model energy code calculations are not with plan set. Comply with the Civano M.E.Code.
06/25/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. A combination Waste and Vent system should not be used in this type of application due to the dirt and sand from the vehicles. Comply with Sec 910.1 UPC1994 Az. Code. NOTE: The vent does not comply with Sec 910.3UPC1994 Az. Code. 2. Provide the total length of new gas line on the plan. 3. Rainwater leaders need to comply with Appendix D3.3 as modified UPC1994 Az. Code.
07/11/2001 MATT FLICK FLOODPLAIN REVIEW Approved
07/26/2001 PATRICIA GEHLEN ZONING REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
10/29/2001 DELMA ROBEY OUT TO CUSTOMER Completed