Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T01CM02437
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/21/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/08/2001 | INGA DAVIDSON | WATER | REVIEW | Approved | |
| 06/11/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 06/11/2001 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 06/13/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/13/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 06/20/2001 | PHIL SEADER | BUILDING-COMMERCIAL | RECEIVED | Denied | |
| 06/20/2001 | MVALDEZ | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 06/21/2001 | MVALDEZ | WWM | REVIEW | Passed | |
| 06/21/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | E1 1) Provide International Energy Conservation Code light budget analysis. Include a detailed description of the lighting fixtures including ballast types and tube types. ( The allowable wt/ft^2 is 2.5) 2) Change the panel callout for the lighting to AP3. E2 1) Provide a lock dog on circuit AP3-26. See 99NEC 700-12(e)exception. 2) Provide the feeder size to panel AP3. In addition provide the service lateral size. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/21/2001 | SUE REEVES | OUT TO CUSTOMER | Completed |