Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T01CM02104
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/10/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | |
05/10/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
05/11/2001 | GERRY KOZIOL | WWM | REVIEW | Approved | |
05/21/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Approved | 1) Unless the shade motors are 1/8 hp or less provide a disconnect within sight of the motor. A 15 or 20 amp single pole switch is sufficient. 99NEC 430-109(c) 2) It appears that the hot water tank load would be 3.3kW per phase. See circuit AG H-6,8,10. 3) Provide the feeder size to each panel. 4) Add a note to the plan to "Provide disconnects for all appliances in accordance with 99NEC 422 part C". 5) For the purposes of determining panel AG load the track lighting must be calculated at a minimum of 150 W/2 ft. 99NEC 220-12(b). Although this appears to increase the panel load if you apply the 65% diversity demand allowed for in article 220-20 for kitchen appliances the total load on panel AG will be reduced. 6) Provide an interlock diagram for HP-1, HP-2, HP-3 and MUA-1. |
05/22/2001 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/22/2001 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |