Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T01CM02104
Parcel: 11711096D

Address:
100 N STONE AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T01CM02104
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
05/10/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved
05/11/2001 GERRY KOZIOL WWM REVIEW Approved
05/21/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Approved 1) Unless the shade motors are 1/8 hp or less provide a disconnect within sight of the motor. A 15 or 20 amp single pole switch is sufficient. 99NEC 430-109(c)
2) It appears that the hot water tank load would be 3.3kW per phase. See circuit AG H-6,8,10.
3) Provide the feeder size to each panel.
4) Add a note to the plan to "Provide disconnects for all appliances in accordance with 99NEC 422 part C".
5) For the purposes of determining panel AG load the track lighting must be calculated at a minimum of 150 W/2 ft. 99NEC 220-12(b). Although this appears to increase the panel load if you apply the 65% diversity demand allowed for in article 220-20 for kitchen appliances the total load on panel AG will be reduced.
6) Provide an interlock diagram for HP-1, HP-2, HP-3 and MUA-1.
05/22/2001 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/22/2001 CINDY AGUILAR OUT TO CUSTOMER Completed