Permit Number: T01CM01983
Parcel: 132171280

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T01CM01983
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/25/2001 PETER MCLAUGHLIN ZONING REVIEW Approved
04/25/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
04/26/2001 JIM EGAN FIRE REVIEW Approved
04/30/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Minimum waste line size for a floor sink is 2" for this use. M-201 2. Provide a cleanout per Sec707.0 UPC1994 Az. Code on the new sink.
04/30/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Show on the plan how the mech. design complies with Chapter 4 IMC 2000. 2. Indicate on the plan what the exhaust fan and fume hood are classified as and show on the plan how the design complies with Chapter 5 IMC 2000. 3. Provide the tonage and amount of rifrigerant the chiller requires on the plan. 4. Provide the manufactures name and listing for the chilled water tank on the plan. NOTE: Tank shall comply with ASME Rules.
05/02/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E-015
1) It appears the circuit breaker serving AH-3- 34,46,38 should be reduced to 90 amps. Page E-80 indicates the feeder serving the transformer is a #4 copper. 99NEC 310-16 75C column.
2) Circuit AH-3-28,30,32 appears in the panel and is part of phase 2 however it does not appear to be on the plan.
3) The panel loads for AL-3 appear to be incorrect.
E-080
1) The one-line indicates panel AL-3 is served with 4# 1/0 1#6 ground. However page #-300 indicates panel AL-3 is served with 4# 2/0, 1# 4 ground. See column E.5, 6.5 on page E-300.
2) The disconnect size shown on the one-line serving panel AL-3 is not consistent with page E-300. Column E.5, 6.5
3) The 70-amp fuse serving panel AL-3 appears to be incorrect. Phase B is loaded to approximately 85 amps.
4) Provide a grounding electrode system for the 45kVA transformer. A minimum #6 copper conductor is required. 99NEC 250-30
5) Provide the lateral size from the utility transformer to the utility pull box serving panels AH-1 and 2.
E-300
1) The transformer appears to be located in a doorway. If it is your intention to suspend the transformer provide a design and structural calculations. Column E, 6.5.
2) The panel prefix serving circuits AH-3-15,17,19-21 appears to be incorrect. The appropriate panel appears to be AL-3. In addition circuit AL-3-21 is utilized twice, once for the smoke detectors and once for general purpose receptacles. Column F.5, 6
3) Provide a disconnect for the door motor. Column F, 5.
99NEC 430-101 and 102.
GENERAL COMMENTS
1) Return the plans I have already reviewed along with your next submission. They are easily recognizable as they are highlighted in yellow marker.
05/04/2001 TGRIFFUS WWM REVIEW Passed
05/04/2001 TGRIFFUS BUILDING-COMMERCIAL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/04/2001 TAMI ACHONG OUT TO CUSTOMER Completed