Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T01CM01968
Parcel: 132171230

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T01CM01968
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2001 JIM EGAN FIRE REVIEW Approved
05/14/2001 DAVID RIVERA ZONING REVIEW Denied
06/11/2001 INGA DAVIDSON WATER REVIEW Approv-Cond
06/13/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Model energy code calculations not with plan set- 1998 I. E. C. C. used. 2. Show on the plan how the mechanical design complies with Chapter 4 IMC 2000. 3. Show the condensate lines, size and discharge location on the plan.
06/13/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Provide a complete waste line isometric drawing of all new work. Provide waste fixtures existing and new on the plan. 2. Provide the manufactures name and listing for all new plumbing fixtures on the plan. 3. Provide the total demand length of the gas line on the plan. 4. Provide combustion air and relief air to the W.H. Per table 5-1 UPC1994 Az. Code. Show on the plan 360 sq. in. each opening. NOTE: Horizontal piping of rainwater has changed, please call 520-791-5550-106 Holly for information.
06/14/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E1.1
1) Provide a fixture cut and catalog number for fixture type D.
2) The North arrow does not appear to be correctly oriented.
3) Provide MEC calculations.
E2.1
1) Provide a disconnect and overload protection for EF2.
2) Provide a note requiring compliance with 99NEC 517-13 on the plan.
E4.1
1) Provide the gutter size for the service.
2) Provide the existing service disconnect ampacity.
3) Provide fault current calculations. Include both the new and existing service disconnects and panels.
E7.1
1) Specification 16111-2.1-B-3 allows PVC conduit under the slab.
99NEC 517-13 prohibits nonmetallic conduit in any patient care areas.
06/25/2001 PHIL SEADER BUILDING-COMMERCIAL REVIEW Denied
07/05/2001 GERRY KOZIOL WWM REVIEW Approved
07/05/2001 LAITH ALSHAMI FLOODPLAIN REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
07/11/2001 SUE REEVES OUT TO CUSTOMER Completed