Permit Number: T01CM01952
Parcel: 105095510

Address:
4701 N STONE AV

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T01CM01952
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2001 JAMES TATE FLOODPLAIN REVIEW Approved
05/10/2001 FRANK KALINSKI WATER REVIEW Passed
05/10/2001 JIM EGAN FIRE REVIEW Denied 1. EMERGENCY FUEL SHUT-OFF SWITCH SHALL NOT CAUSE A FIRE ALARM SIGNAL TO BE TRANSMITTED TO OFF PREMISES ALARM MONITORING AGENCY. NOR SHALL IT CAUSE ANY FIRE ALRM FUNCTION TO BE PERFORMED IN THE EXISTING SAM'S CLUB BUILDING.
2. INSTALLATION OF UST'S, PRODUCT PIPING AND DISPENSERS REQUIRES SEPARATE PERMITS AND SUBMITTALS BY THE LICENSED CONTRACTOR RESPONSIBLE FOR THE INSTALLATION.
05/23/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
05/23/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Passed
06/08/2001 PHIL SEADER BUILDING-COMMERCIAL REVIEW Denied
06/11/2001 DAN CASTRO ZONING REVIEW Denied
06/13/2001 GERRY KOZIOL WWM REVIEW Passed
07/02/2001 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved Provide the following
1.complete fault current analysis
2.Add 25% for continuous loads (lights,etc.) and largest motor
3.Provide fixture cut sheet-sheets of the canopy lights including horizontal cutoff,wattage of lamps and total watts including ballast,type of lamp,mounting etc.
4.Provide M.E.C. light calculations
5.Fixture lense should be flush or recessed for compliance with the local lighting ordinance or canopy must extend below the fixture lense.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/26/2001 JKOZUCH OUT TO CUSTOMER Completed