Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T01CM01952
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/30/2001 | JAMES TATE | FLOODPLAIN | REVIEW | Approved | |
| 05/10/2001 | FRANK KALINSKI | WATER | REVIEW | Passed | |
| 05/10/2001 | JIM EGAN | FIRE | REVIEW | Denied | 1. EMERGENCY FUEL SHUT-OFF SWITCH SHALL NOT CAUSE A FIRE ALARM SIGNAL TO BE TRANSMITTED TO OFF PREMISES ALARM MONITORING AGENCY. NOR SHALL IT CAUSE ANY FIRE ALRM FUNCTION TO BE PERFORMED IN THE EXISTING SAM'S CLUB BUILDING. 2. INSTALLATION OF UST'S, PRODUCT PIPING AND DISPENSERS REQUIRES SEPARATE PERMITS AND SUBMITTALS BY THE LICENSED CONTRACTOR RESPONSIBLE FOR THE INSTALLATION. |
| 05/23/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/23/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 06/08/2001 | PHIL SEADER | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 06/11/2001 | DAN CASTRO | ZONING | REVIEW | Denied | |
| 06/13/2001 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 07/02/2001 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | Provide the following 1.complete fault current analysis 2.Add 25% for continuous loads (lights,etc.) and largest motor 3.Provide fixture cut sheet-sheets of the canopy lights including horizontal cutoff,wattage of lamps and total watts including ballast,type of lamp,mounting etc. 4.Provide M.E.C. light calculations 5.Fixture lense should be flush or recessed for compliance with the local lighting ordinance or canopy must extend below the fixture lense. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/26/2001 | JKOZUCH | OUT TO CUSTOMER | Completed |