Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2001 JIM EGAN FIRE REVIEW Approved
04/20/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
04/20/2001 DAN CASTRO ZONING REVIEW Approved
04/25/2001 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved 1.W.Heater is shown as cir.L-2(11),but panel schedule shows it as cir.L-1(11).
2.Evap. cir.M-40 is a spare accoding to the panel schedule.
3.Panel M needs to be re-calculate.
4.Recalculate c phase circuits for panel L-2
5.Circuit all receptacles at office partitions.
6.L-1 cir.29 should be calculated at 1000 watts not 360 watts.
04/30/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved Plumbing design does not comply with Sec905.3 UPC1994
04/30/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved No appeal to the building offical with plans.
05/01/2001 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied
05/01/2001 GERRY KOZIOL WWM REVIEW Approved