Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T01CM01770
Parcel: 13312006M

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T01CM01770
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2001 PETER MCLAUGHLIN ZONING REVIEW Approved
04/18/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
04/24/2001 JIM EGAN FIRE REVIEW Approved
04/25/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. If AC 1,2 &3 are gas fired- Where is the gas line? Provide total length, input, &size on the plan. 2. Access to the water heaters shall comply with Sec 511.2UPC1994 Az. Code NOTE: Sign and date seals on the P-1 &P-2 sheets.
04/25/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Architect of record shall provide a complete detail of the construction, support of the 1hr chase and the support of the hood from the structure. 2. Provide the manufactures name and listing for the exhaust fans and hoods on the plan. NOTE: Hoods shall have a UL710 listing. 3. Show on the plan how the mech. design complies with Chapter 4 IMC 2000. NOTE: Fire suppression system shall be installed by a Qualified contractor with a L-16 License.
04/27/2001 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
05/03/2001 PHIL SEADER BUILDING-COMMERCIAL REVIEW Denied
05/07/2001 GERRY KOZIOL WWM REVIEW Approved
05/07/2001 TOM CLARK WATER REVIEW Approv-Cond

Final Status

Task End Date Reviewer's Name Type of Review Description
05/17/2001 JKOZUCH OUT TO CUSTOMER Completed
05/08/2001 DELMA ROBEY REJECT SHELF Completed