Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T01CM01770
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/18/2001 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
04/18/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
04/24/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
04/25/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. If AC 1,2 &3 are gas fired- Where is the gas line? Provide total length, input, &size on the plan. 2. Access to the water heaters shall comply with Sec 511.2UPC1994 Az. Code NOTE: Sign and date seals on the P-1 &P-2 sheets. |
04/25/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Architect of record shall provide a complete detail of the construction, support of the 1hr chase and the support of the hood from the structure. 2. Provide the manufactures name and listing for the exhaust fans and hoods on the plan. NOTE: Hoods shall have a UL710 listing. 3. Show on the plan how the mech. design complies with Chapter 4 IMC 2000. NOTE: Fire suppression system shall be installed by a Qualified contractor with a L-16 License. |
04/27/2001 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
05/03/2001 | PHIL SEADER | BUILDING-COMMERCIAL | REVIEW | Denied | |
05/07/2001 | GERRY KOZIOL | WWM | REVIEW | Approved | |
05/07/2001 | TOM CLARK | WATER | REVIEW | Approv-Cond |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/17/2001 | JKOZUCH | OUT TO CUSTOMER | Completed |
05/08/2001 | DELMA ROBEY | REJECT SHELF | Completed |