Permit Number: T01CM01655
Parcel: 11105026C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T01CM01655
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2001 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1) PROVIDE DESIGN AND CODE REVIEW CHECKLIST PER 2000 IBC. S2) PROVIDE CROSS-SECTION THROUGH WALL SHOWING MATERIALS OF CONSTRUCTION, INCLUDING CONNECTION TO STRUCTURE ABOVE AND BELOW W/ FASTENER TYPE, SIZE, SPACING/ NUMBER. S3) PROVIDE DESIGN AND DETAILS FOR CEILING IN TOILET ROOM. S4) PROVIDE COMPLETE DETAILS FOR ACCESSIBILE TOILET ROOM, INCLUDING LOCATING EACH FIXTURE ,SHOWING CLEAR AREAS AT FIXTURES,INCLUDING 60" DIAMETER TURNAROUND CLEAR OF DOOR SWINGS. S5) PROVIDE COMPLETE FLOOR PLAN FOR SUITE #3138, INCLUDING ADJACENT SPACE ATTACHED TO THIS SPACE. S6) CLARIFY WHERE 20% OF EACH PROJECT BUDGET IS SPENT ON ACCESSIBILITY PER IBC CHAPTER #11 AND #34.
04/09/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
04/09/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Approved
04/09/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved
04/12/2001 JIM EGAN FIRE REVIEW Approved
04/13/2001 GERRY KOZIOL WWM REVIEW Approved
04/13/2001 MVALDEZ ZONING REVIEW Needs Review
04/13/2001 MVALDEZ FLOODPLAIN REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/01/2001 MONICA VALDEZ OUT TO CUSTOMER Completed