Permit Number: T01CM01585
Parcel: 10510010D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T01CM01585
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2001 JIM EGAN FIRE REVIEW Approved
04/04/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Passed
04/04/2001 DAN CASTRO ZONING REVIEW Approved
04/04/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
04/04/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied
04/11/2001 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied
04/11/2001 DROBEY WWM REVIEW Passed
04/11/2001 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied Comments from 4/4/01 by Bob Suba
1) Show the transformer locations on the electrical floor plan.
Response: OK
2) Provide load calculation; drive the load all the way back to service equipment.
Response: Not addressed
3) Provide circuit and load for 9 new PL lights and 7 new 2x2 fluorescent fixtures.
Response: Not addressed

Comments from 4/10/01 by Randy Schuler
E-2
1) Circuits RP5E (22,24) (26,28) (30,32) (34,36) should circuit to panel RP5EB. (column 7B)
2) Circuit RP5W 25,27,29 should circuit to LP5W. (column 6.5B)
3) Circuit RP5WA (26,28,30)(32,34,36) should circuit to RP5W. (column 2B)
E-3
1) The keynote #17 should read "Connect to the unswitched side of the lighting circuit nearest to the exit/emergency light. This will insure compliance with 99NEC 700-12(e)

Final Status

Task End Date Reviewer's Name Type of Review Description
04/11/2001 DELMA ROBEY OUT TO CUSTOMER Completed