Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T01CM01550
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/02/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
| 04/02/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 04/30/2001 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 05/29/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/29/2001 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.show fixture circuiting on new florescent fixtures 2. show details on outdoor wall pack with lense discription 3. give ballast amperages for flor. fixtures and include on panel schedule 4. show fixture detail for type A fixtures showing fixture and lense 5. indicate required EYS fittings ( at both ends of conduits)that are routed in or through the classified location 6. indicate the existing service lateral conductor sizes,conduit size,type insulation,cu. or aluminum conductors |
| 05/29/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/06/2001 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 06/07/2001 | GERRY KOZIOL | WWM | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/15/2001 | SUE REEVES | OUT TO CUSTOMER | Completed |