Permit Number: T01CM01550
Parcel: 137051130

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T01CM01550
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2001 JIM EGAN FIRE REVIEW Approved
04/02/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
04/30/2001 DAN CASTRO ZONING REVIEW Approved
05/29/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
05/29/2001 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.show fixture circuiting on new florescent fixtures
2. show details on outdoor wall pack with lense discription
3. give ballast amperages for flor. fixtures and include on panel schedule
4. show fixture detail for type A fixtures showing fixture and lense
5. indicate required EYS fittings ( at both ends of conduits)that are routed in or through the classified location
6. indicate the existing service lateral conductor sizes,conduit size,type insulation,cu. or aluminum conductors
05/29/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved
06/06/2001 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied
06/07/2001 GERRY KOZIOL WWM REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
06/15/2001 SUE REEVES OUT TO CUSTOMER Completed