Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T01CM01520
Parcel: 125011230

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T01CM01520
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Approved E3
1) Circuits UP-(1,2) (3,4) (5,6) (7,8) (9,10) require an additional neutral.
2) Provide a disconnect for the hot water circuits or provide a circuit breaker lockout device. See U-(17,19) (21,23) (25,27). 99NEC 422-31(b).
3) Circuit U-35,37 should be U-33,35.
E7
4) Please clarify the UPS design. There appear to be several inconsistencies. Provide a design that meets NEC requirements and is consistent throughout. In addition provide the UPS kVA rating.
5) A/C load is specified as 70.6 amps therefore the kVA per phase is 9.8.
6) The load calculations appear to be incorrect. The total 3 phase load must be added to the total 1 phase load. Thus the service is loaded to approximately 454 amps.
7) Please provide the service entrance conductor size.
8) The A and C phase should be utilized for all 120/240 loads. 99NEC 384-3(f)
04/12/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
04/12/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved
04/16/2001 BOB SUBA ELECTRICAL-COMMERCIAL review Approved E3
1) Circuits UP-(1,2) (3,4) (5,6) (7,8) (9,10) require an additional neutral.
2) Provide a disconnect for the hot water circuits or provide a circuit breaker lockout device. See U-(17,19) (21,23) (25,27). 99NEC 422-31(b).
3) Circuit U-35,37 should be U-33,35.
E7
4) Please clarify the UPS design. There appear to be several inconsistencies. Provide a design that meets NEC requirements and is consistent throughout. In addition provide the UPS kVA rating.
5) A/C load is specified as 70.6 amps therefore the kVA per phase is 9.8.
6) The load calculations appear to be incorrect. The total 3 phase load must be added to the total 1 phase load. Thus the service is loaded to approximately 454 amps.
7) Please provide the service entrance conductor size.
8) The A and C phase should be utilized for all 120/240 loads. 99NEC 384-3(f)
04/16/2001 PATRICIA GEHLEN ZONING REVIEW Denied
04/16/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/17/2001 MVALDEZ OUT TO CUSTOMER Completed