Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T01CM01520
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/11/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Approved | E3 1) Circuits UP-(1,2) (3,4) (5,6) (7,8) (9,10) require an additional neutral. 2) Provide a disconnect for the hot water circuits or provide a circuit breaker lockout device. See U-(17,19) (21,23) (25,27). 99NEC 422-31(b). 3) Circuit U-35,37 should be U-33,35. E7 4) Please clarify the UPS design. There appear to be several inconsistencies. Provide a design that meets NEC requirements and is consistent throughout. In addition provide the UPS kVA rating. 5) A/C load is specified as 70.6 amps therefore the kVA per phase is 9.8. 6) The load calculations appear to be incorrect. The total 3 phase load must be added to the total 1 phase load. Thus the service is loaded to approximately 454 amps. 7) Please provide the service entrance conductor size. 8) The A and C phase should be utilized for all 120/240 loads. 99NEC 384-3(f) |
04/12/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | |
04/12/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
04/16/2001 | BOB SUBA | ELECTRICAL-COMMERCIAL | review | Approved | E3 1) Circuits UP-(1,2) (3,4) (5,6) (7,8) (9,10) require an additional neutral. 2) Provide a disconnect for the hot water circuits or provide a circuit breaker lockout device. See U-(17,19) (21,23) (25,27). 99NEC 422-31(b). 3) Circuit U-35,37 should be U-33,35. E7 4) Please clarify the UPS design. There appear to be several inconsistencies. Provide a design that meets NEC requirements and is consistent throughout. In addition provide the UPS kVA rating. 5) A/C load is specified as 70.6 amps therefore the kVA per phase is 9.8. 6) The load calculations appear to be incorrect. The total 3 phase load must be added to the total 1 phase load. Thus the service is loaded to approximately 454 amps. 7) Please provide the service entrance conductor size. 8) The A and C phase should be utilized for all 120/240 loads. 99NEC 384-3(f) |
04/16/2001 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | |
04/16/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/17/2001 | MVALDEZ | OUT TO CUSTOMER | Completed |