Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T01CM01509
Parcel: 117170110

Address:
135 S 6TH AV

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T01CM01509
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2001 JIM EGAN FIRE REVIEW Denied
04/16/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
04/19/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Show the gas meter and gas line going to the equipment on the plan. Provide the size.
04/19/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied 1) Please add a note to the plan regarding series rating requirements covering the fuses and downstream panel board. The 99NEC 90-7,110-3(a)(b), 110-9, 110-10, 110-22 and 240-86(a)(b) requires that a fully integrated listed/labeled series rated system be utilized. Series rated systems listed and labeled by 3rd party testing laboratories such as UL is required.
2) Provide a complete interlock diagram for the make-up and exhaust fans.
Please see 99NEC 430-74, 430-101 and 430-102 for special requirements.
04/19/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. The architect of record shall provide a complete detail of the 1 hour chase for the type I hood. This will inclued the construction, support of the chase, hood, and duct work from the structure. NOTE: A 1 hour ceiling is required above the hood and extending 18" beyond all sides of the hood. 2. Show on the plan how the refrigeration lines get to the fan coil from the condensing unit. provide the size.
05/01/2001 PHIL SEADER BUILDING-COMMERCIAL REVIEW Denied
05/15/2001 INGA DAVIDSON WATER REVIEW Approv-Cond
05/17/2001 PATRICIA GEHLEN ZONING REVIEW Denied
05/17/2001 GERRY KOZIOL WWM REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
05/21/2001 MONICA VALDEZ OUT TO CUSTOMER Completed