Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2001 JIM EGAN FIRE REVIEW Approved
06/25/2001 TOM WEIDEMAN FLOODPLAIN REVIEW Denied see engineering comments
06/25/2001 TOM WEIDEMAN ENGINEERING REVIEW Denied DATE: June 25, 2001

FROM: Engineering Section

SUBJECT: T01CM01474
La Paloma Family Services Common Building

RECEIVED: June 21, 2001

COMMENTS: The Site Plan and Revised Drainage Statement have been reviewed and rejected - see
comments below.

Site Plan Comments

1. Provide sufficient elevation shots and drainage pattern information to demonstrate conveyance of rooftop and parking lot drainage into storm water harvesting areas as previously requested.
2. Show and dimension the Blacklidge Drive right-of-way. Call out and identify the street centerline. Show dimensions from the centerline to existing curb, sidewalk, etc. as previously requested.
3. (H.P.)Show and call out existing drainage patterns (including water harvesting) across the property, proposed and existing finish floor elevations and finish grades as previously requested and in accordance with the elevations described in the floodplain use permit.
4. Provide existing topographic contours at intervals not exceeding two feet and/or spot elevations as pertinent and a bench mark based on City of Tucson datum including City field book and page number as previously requested.
5. (H.P.)Show and call out all offsite to onsite flow acceptance points with corresponding Q100 flow quantities as previously requested.
6. (H.P.)Show and provide two appropriate sized openings in the new masonry wall surrounding the development per item 3 of the floodplain use permit.
7. Please provide the requested information on the site plan sheets of the submittal.



Drainage Statement Comments

1. Revise the statement to specifically call out designated water harvesting areas that will accept runoff from the roof tops and parking lot areas per the special exception land use conditions.
2. (Added) Call out the floodplain use permit requirements.
3. (H.P.)Revise the statement to identify how the new perimeter wall will impact the site. Provide offsite to onsite flow acceptance points with corresponding Q100 flow quantities.
4. (H.P.)Demonstrate that a minimum of two wall openings will be needed to convey drainage thru the property per the floodplain use permit requirements. Provide the appropriate calculations to size the openings.
5. Provide a current 200-scale aerial photo-topo map showing the subject parcel, contributing drainage areas and points of concentration and other pertinent information related to the site as previously requested.
6. Please be advised that a complete revised drainage statement is required to be re-submitted which addresses all comments.



Items Required: Revised Site Plan and Revised Drainage Statement
Re-submittal Required: Yes

If you have any questions on the above comments feel free to call Tom Weideman at 791-4942. My E-mail address is TWeidema@ci.tucson.az.us.



Reviewer: Laith Alshami, P.E.
Tom Weideman Engineering Section
Senior Engineering Associate
Development Review
06/25/2001 TOM WEIDEMAN SANITATION REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/26/2001 MONICA VALDEZ OUT TO CUSTOMER Completed