Permit Number: T01CM01474
Parcel: 113072100

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T01CM01474
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/28/2001 JIM EGAN FIRE REVIEW Denied
04/09/2001 PETER MCLAUGHLIN ZONING REVIEW Denied
05/09/2001 JKOZUCH FLOODPLAIN REVIEW Denied
05/16/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1.Provide the size of the existing sewer on the sheet C-1.1 at each segment of the line. NOTE: Waste fixture units for water closets will be 6 fu (ea) in the 1994 UPC Az. Code. 2. F.F.E. should be on sheet C-1.1. 3. A kitchen sink in a commercial application is 3fu. 4. Provide a water demand calculation based on Appendix A UPC 1994 Az. Code. 5. Provide an expansion tank on the water heater Per Sec608.3 Par 3 UPC 1994 Az. Code.
05/16/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Model Energy Code calculations not with plan set. 2. Show on the plan how the mech. design complies with Chapter 4 IMC 2000. 3. Combustion Air shall be obtained from outside Per Sec 507.3.1 UPC 1994 Az. Code. NOTE: The ceiling can not exceed 16" above the top of the door. The grills in the door shall have a free air opening of 130 sq. in. each opening. 4. Ahood will be required over the range Per Sec 507.2.2 IMC 2000. Make-up air shall comply with Sec 508 IMC 2000.
05/23/2001 PHIL SEADER BUILDING-COMMERCIAL REVIEW Denied
05/24/2001 WATER WATER REVIEW Approved
05/29/2001 GERRY KOZIOL WWM REVIEW Approved
06/16/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/30/2001 JKOZUCH REJECT SHELF Completed
05/29/2001 DELMA ROBEY OUT TO CUSTOMER Completed