Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T01CM01468
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/21/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 11/24/2003 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. City of Tucson Ordinance 1802 requires a reduced pressure backflow preventer to be located immediately after the water meter. The drawings indicate a double check valve has been used in the design (Wilkins model 950XLT); please revise and include the new pressure drop on the water calculations. 2. One of the specified fixtures (Bradley emergency shower) requires a minimum pressure greater than the 15 PSI used in the water pipe sizing calculations. Revise calculations and resize piping as necessary. Reference Section 608.1, UPC 1994. 3. The domestic cold water system is protected from the Industrial Cold Water (ICW) system with a reduced pressure backflow preventer. If the ICW is a non-potable system, construct and label the system in accordance with Section 603.3.11, UPC 1994. |
| 11/24/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/25/2003 | DOUG WILLIAMS | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/02/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 11/28/2003 | TAMI ACHONG | REJECT SHELF | Completed |