Permit Number: T01CM01468
Parcel: 106101650

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T01CM01468
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/21/2003 JIM EGAN FIRE REVIEW Approved
11/24/2003 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. City of Tucson Ordinance 1802 requires a reduced pressure backflow preventer to be located immediately after the water meter. The drawings indicate a double check valve has been used in the design (Wilkins model 950XLT); please revise and include the new pressure drop on the water calculations.
2. One of the specified fixtures (Bradley emergency shower) requires a minimum pressure greater than the 15 PSI used in the water pipe sizing calculations. Revise calculations and resize piping as necessary. Reference Section 608.1, UPC 1994.
3. The domestic cold water system is protected from the Industrial Cold Water (ICW) system with a reduced pressure backflow preventer. If the ICW is a non-potable system, construct and label the system in accordance with Section 603.3.11, UPC 1994.
11/24/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/25/2003 DOUG WILLIAMS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2003 TAMI ACHONG OUT TO CUSTOMER Completed
11/28/2003 TAMI ACHONG REJECT SHELF Completed