Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T01CM01468
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/22/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Denied | |
06/26/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/27/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Engineer of record shall seal the memorandum from Jeff Lape and address the following - wall areas are not the same ie; N&S - E&W recalculate. Architectural drawings do not reflect calculations. 2. Evaporative cooler does not comply with Sec 317.6 #2 UMC1994. 3. Provide access to the mechanical equipment on the roof per Sec321 UMC1994. |
06/27/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. Provide a detail of the access required for the backwater valve on the plan. 2. Provide the listings for all of the plumbing fixtures on the plan. 3. What is ICW on the plumbing plan P1.01 ? Whay are you using a 3" disc meter on a 2" line ? 4. Provide a trap primer on all of the F.D.s & F.S.s per Sec 1007.0 UPC1994. |
07/23/2001 | GERRY KOZIOL | WWM | REVIEW | Denied | |
07/23/2001 | PHIL SEADER | BUILDING-COMMERCIAL | REVIEW | Approved | |
07/24/2001 | PATRICIA GEHLEN | ZONING | REVIEW | Denied |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/30/2001 | SUE REEVES | OUT TO CUSTOMER | Completed |