Permit Number: T01CM01454
Parcel: 120087810

Review Status: Completed

Review Details: SITE

Permit Number - T01CM01454
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2001 STEVE TINEO ENGINEERING REVIEW Denied See previous comments 1, 3, 7, and 9 of the second submittal in permits-plus.
07/19/2001 ESTEVAN TINEO FLOODPLAIN REVIEW Denied We do not reccomend approval of the report; the next submittal, at a minimum, should address the following comments.

1. The report mentions that the project is within a balanced basin; this is not correct, the project is located in a non-designated basin, please revise.

2. The report must include the supporting data used to determine the contributiong watershed impacting the site. Include the topographic maps, with the appropriate watershed delienations, used to determine offsite flows.

3. The calcualtions and assumptions used to determine that the existing storm drain will convey offsite flow is not sufficient. Provide storm drain calculations, including hydraulic grade line and starting tail-water, demonstrating that the proposed development is not impacted by offsite flow. Provide all supporting data, including as-built info and location of the existing storm drain, and supporting calcs.
07/19/2001 STEVE TINEO SANITATION REVIEW Denied See previous comment in permit plus, second submittal; Development must provide onsite refuse collection per DS 6-01. Revise, and demonstrate access.
07/26/2001 PATRICIA GEHLEN ZONING REVIEW Denied
07/30/2001 PATRICIA GEHLEN LANDSCAPE REVIEW Denied 1. Dimension the 13th Avenue street landscape border on Sheets L1 and L2. LUC 3.7.2.4.//////
2. Provide one canopy tree for each/33 feet within the 13th Avenue street landscape border on Sheets L1 and L2.//////
3. Indicate the location of the the future landscape border location on site plan sheet 2 per LUC 2.8.3.5.////////////
4. A 30' screen is required on the development side of the 13th Avenue border. Show the required screening on sheets L1 and L2. LUC Table 3.7.2-I.///////////////////////////
08/01/2001 PHIL SEADER HANDICAP-SITE REVIEW Denied
08/01/2001 JOE LINVILLE NPPO REVIEW Approved Exception approved 5/16/01.
08/02/2001 JIM EGAN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/03/2001 SUE REEVES OUT TO CUSTOMER Completed