Permit Number: T01CM01375
Parcel: 106060180

Address:
1300 W PRINCE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T01CM01375
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/12/2001 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1) PROVIDE COMPLETED CODE REVIEW CHECKLIST BY ARCHITECT OF RECORD. S2) AT WALL DETAILS PROVIDE CONNECTION DETAILS TO STRUCTURE ABOVE AND BELOW INCLUDING FASTENER TYPE , SIZE , SPACING /NUMBER. S3) SHOW CONNECTIONS TO JAMB AND HEAD AT INFILL AT 1 HR OPENING INFILL.
S4) SPECIAL INSPECTION REQUIRED FOR EPOXY ANCHORS, SEE ATTACHED CERTIFICATE/ WEBSITE. S5) PROVIDE NAME AND MODEL NUMBER FOR CEILING SUSPENSION SYSTEM OR FULLY DETAIL ON DRAWINGS. S6) REVISE VESTIBULE DOOR AT WEST SIDE ie: NO DOOR .
04/16/2001 TGRIFFUS WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/16/2001 TAMI ACHONG OUT TO CUSTOMER Completed