Review Details: COMMERCIAL TI

Permit Number - T01CM01296
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2001 SREEVES FIRE REVIEW Approved
07/10/2001 CRAIG GROSS ZONING REVIEW Completed
09/12/2001 SREEVES WWM REVIEW Passed
09/13/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
09/13/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved
09/17/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E2.1
1) It does not appear the inter duct within the 3" conduit can be properly sealed to prevent the transmission of gases from one environment to the next. See notes 8 and 21. This issue appears 3 times on the plan. See 99NEC 502-1 and FPN note 2. See POWER & SYSTEM PLAN, ELECTRICAL ROOM ELEVATION, and key note schedule
2) The compressor disconnect lacks proper work clearance. See POWER & SYSTEM PLAN, and the key note schedule. See 99NEC 110-26
3) Reserved
4) Reserved
5) It appears tag note 16 at the front of the fuel tank pointed to the 3 conduits routed to panel L should be tag note 7. See POWER & SYSTEM PLAN, ELECTRICAL ROOM ELEVATION, and key note schedule.
6) It appears tag note 2 pointed to the 4 conduits from the monitor wells to the Veeder Root system should be tag note 20. See ELECTRICAL ROOM ELEVATION and key note schedule.
7) Provide catalog cut with catalog numbers for fixture type B.
E3.1
1) Remove the equipment ground from the service lateral only. As shown the equipment ground serves no purpose and is in parallel with the neutral. See 99NEC 250-30(a)(1)ex1, 250-32(b)1 [in principal], 310-4 and 347-4ex2.
09/28/2001 DROBEY FLOODPLAIN REVIEW Needs Review
09/28/2001 DROBEY WATER REVIEW Needs Review
09/28/2001 DROBEY BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/28/2001 DELMA ROBEY OUT TO CUSTOMER Completed