Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T01CM01296
Parcel: 13612004L

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T01CM01296
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2001 JIM EGAN FIRE REVIEW Denied 1. FIRE HYDRANT REQUIRED.
2. DISPENSING FROM UL142 TANKS NOT PERMITTED. ALL REFERENCES TO ABOVEGROUND FUEL TANKS SHOULD SPECIFY UL 2085 (PROTECTED ABOVEGROUND TANK) OR VAULTED TANK.
05/11/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Denied Provide copy of approved site and/or grading plan for reference.
05/14/2001 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/22/2001 JKOZUCH OUT TO CUSTOMER Completed
05/14/2001 JKOZUCH REJECT SHELF Completed