Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T01CM01296
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/11/2001 | JIM EGAN | FIRE | REVIEW | Denied | 1. FIRE HYDRANT REQUIRED. 2. DISPENSING FROM UL142 TANKS NOT PERMITTED. ALL REFERENCES TO ABOVEGROUND FUEL TANKS SHOULD SPECIFY UL 2085 (PROTECTED ABOVEGROUND TANK) OR VAULTED TANK. |
05/11/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Denied | Provide copy of approved site and/or grading plan for reference. |
05/14/2001 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/22/2001 | JKOZUCH | OUT TO CUSTOMER | Completed |
05/14/2001 | JKOZUCH | REJECT SHELF | Completed |