Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T01CM01268
Parcel: 11521010E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T01CM01268
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2001 DAN CASTRO ZONING REVIEW Approved
03/16/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
03/16/2001 JIM EGAN FIRE REVIEW Approved
03/20/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied PROVIDE THE TOTAL LENGTH OF GAS LINE ON THE PLAN.
03/20/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1.The Architect of record shall show all rated walls, ceilings and corridors on the plan. 2. M-2 indicates that there will be Fire/Smoke dampers in the corridor. If this a required exit (rated corridor) then provide a fire/smoke damper for the return air grill for AC-1. 3. Condesate can not discharge over grade unless the ground can absorb it without standing water. 4. All concrete pans are to be 3" above grade Sec1105.2.1 UMC1994 5. Provide the total length of gas line on the plan. 6. Insulation of duct work exposed in an attic shall have a R-6 value, note this on the plan.
03/23/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E2
1) Circuits PP-S-2 , PP-NW-2 and PP-S-6 require OL, SC, and Disconnects within sight. In addition indicate both the circuit breaker and conductor sizes. See 99NEC 210, 220,310-16, and 430.
2) Provide the full load data for the HP's. Page M3 indicates a 1 ton HP, 3.5KW heating and a blower motor. Thus it would appear the loads in the panel are incorrect and as such all subsequent loads are also incorrect. In addition the fault currents may also be affected. See 99NEC 424-3 which requires the circuit to be sized at 1.25% of the total equipment load.
04/17/2001 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied
04/19/2001 DROBEY WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
10/10/2001 JKOZUCH OUT TO CUSTOMER Completed