Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T01CM01268
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/14/2001 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 03/16/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 03/16/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/20/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | PROVIDE THE TOTAL LENGTH OF GAS LINE ON THE PLAN. |
| 03/20/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1.The Architect of record shall show all rated walls, ceilings and corridors on the plan. 2. M-2 indicates that there will be Fire/Smoke dampers in the corridor. If this a required exit (rated corridor) then provide a fire/smoke damper for the return air grill for AC-1. 3. Condesate can not discharge over grade unless the ground can absorb it without standing water. 4. All concrete pans are to be 3" above grade Sec1105.2.1 UMC1994 5. Provide the total length of gas line on the plan. 6. Insulation of duct work exposed in an attic shall have a R-6 value, note this on the plan. |
| 03/23/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | E2 1) Circuits PP-S-2 , PP-NW-2 and PP-S-6 require OL, SC, and Disconnects within sight. In addition indicate both the circuit breaker and conductor sizes. See 99NEC 210, 220,310-16, and 430. 2) Provide the full load data for the HP's. Page M3 indicates a 1 ton HP, 3.5KW heating and a blower motor. Thus it would appear the loads in the panel are incorrect and as such all subsequent loads are also incorrect. In addition the fault currents may also be affected. See 99NEC 424-3 which requires the circuit to be sized at 1.25% of the total equipment load. |
| 04/17/2001 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 04/19/2001 | DROBEY | WWM | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/10/2001 | JKOZUCH | OUT TO CUSTOMER | Completed |