Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T01CM01188
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/12/2001 | JIM EGAN | FIRE | REVIEW | Approved | 1. BATTERY SYSTEMS SHALL COMPLY WITH 1997 UNIFORM FIRE CODE ARTICLE 64. 2. SEPARATE PERMIT REQUIRED FOR INSTALLATION OF ABOVEGROUND FUEL STORAGE TANKS. |
03/26/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | E1 1) Keynote 3 indicates a relocation and connection to an existing well disconnect which is referenced on E2 by keynote 3. Please clarify the location of the equipment on E2. E2 1) Identify all the equipment connected to panel DP by utilizing an alpha designation that corresponds with page E3 feeder legend. 2) Provide a motor rated switch with appropriately sized overloads for FSD. In addition add a 15 amp circuit breaker in the panel. See page E4 circuit CO-B-37. 3) Clarify the intent of the term "Switch Lites". See keynote 24, typical of 7 circuits. 4) Keynote 11 references an air dryer however the keynote on the plan points to TU-1. 5) There are 2 keynotes 30 in the keynote legend. E3 1) The fuse protecting the primary of T1 is too small. 2) SP1 and SP2 are shown as 2HP however on M2 they are specified as 5HP. 3) Remove the bonding jumper from the neutral to ground in panel RP. Provide a ground wire in the feeder. As shown the neutral and the conduit are in parallel and will each carry a portion of the current. E4 1) Reduce circuit CO-B-5 to 15 amps. 2) It appears circuits CO-B-7, 9,11,21,29,31,33,35 are existing. Please clarify. 3) Please provide the Z of T1. |
03/30/2001 | JKOZUCH | FLOODPLAIN | REVIEW | Needs Review | |
03/30/2001 | DAVID RIVERA | ZONING | REVIEW | Denied | |
03/30/2001 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | |
04/03/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Passed | |
04/03/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | |
04/17/2001 | JKOZUCH | WWM | REVIEW | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/17/2001 | JKOZUCH | OUT TO CUSTOMER | Completed |
04/17/2001 | JKOZUCH | REJECT SHELF | Completed |
04/17/2001 | JKOZUCH | APPROVAL SHELF | Completed |
04/17/2001 | JKOZUCH | REJECT SHELF | Completed |