Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T01CM01069
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/29/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
| 05/29/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approv-Cond | Plumbing See comments on the back of the application. |
| 05/29/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 06/06/2001 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 06/08/2001 | GERRY KOZIOL | WWM | REVIEW | Denied | |
| 06/08/2001 | DAN CASTRO | ZONING | REVIEW | Denied | |
| 06/08/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Denied | Denied for Engineering - parking in ROW requires TRE from Real Estate Div. |
| 07/27/2001 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. provide fixture schedule and fixture cut sheets with number and wattages of lamps and total watts of fixture including the ballast, the type of lamp (incandescent , florescent , etc.) , outdoor lighting to comply with outdoor lighting ordinance . When this is provided I can review the load and calculations .It is not clear that the outdoor lighting is in compliance with the outdoor lighting ordinance.Please provide lamp type and a cut sheet of the outdoor fixtures so that this can be determined. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/14/2001 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |