Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T01CM01058
Parcel: 137052260

Address:
701 W IOWA ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T01CM01058
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2001 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T01CM01058
3/14/01

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating the action taken.

GENERAL REQUIREMENTS:

1. All corrections and revisions shall be made on the original tracings. Return all redlined prints. The final package shall consist of two sets of drawings and related documents, one which the City shall retain and the other set will be stamped and returned to you.

2. To avoid delays, ensure all corrections have been made, are complete and have been coordinated on all applicable details and notes.

STRUCTURAL PLANS:

1. 1-#4 REBAR IS MISSING IN BOND BEAMS AT TOP OF MASONRY WALLS

ELEVATIONS:

1. Show calculation of attic ventilation area in compliance with R806.2. Note SIZE AND LOCATION of all vents needed to comply.

PLUMBING PLANS:

1. Gas: Provide the length of line to each appliance, BTU demand of each appliance, size of each branch, total demand and size of the meter. See G2412 and Tables G2412.3(1) through G2412.3(6).---also water heater and 2nd furnace
GAS LINE SIZES AS INDICATED DO NOT MEET CODE REQUIREMENTS

ELECTRICAL PLANS:

1. Note that two or more 20-amp small appliance circuits shall be provided to serve all receptacle outlets ON THE KITCHEN COUNTERS Such circuits shall have no other outlets, per E3603.2 and E3801.---------ALL RECPTS ON KITCHEN COUNTER ARE TO BE GFCI AND ON TWO SEPARATE CIRCUITS. WHAT CIRCUIT ARE THE KITCHEN LIGHTS ON?


MODEL ENERGY CODE:

1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11.

2. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS
AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS: @ 791-5550 EXT. 112

Final Status

Task End Date Reviewer's Name Type of Review Description
08/10/2001 CINDY AGUILAR OUT TO CUSTOMER Completed