Permit Number: T01CM01057
Parcel: 12213125A

Address:
1345 N BRYANT AV

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T01CM01057
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2001 DAVID RIVERA ZONING REVIEW Approved
03/08/2001 DRIVERA NPPO REVIEW Passed
03/08/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
03/21/2001 DAVE WILLETT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T01CM01057

03/20/01

PLEASE ADDRESS THE FOLLOWING COMMENTS. RESUBMIT TWO SETS OF CORRECTED PLANS. SUBMIT A COPY OF THIS LETTER , NOTING THE DETAIL AND OR SHEET WHERE THE CORRECTION MAY BE FOUND.


GENERAL REQUIREMENTS

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUELINE SHALL BE RETURNED.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

4. ALL PLANS SHALL BE LEGIBLE AND NO SCALE SMALLER THAN 1/4"=1'-0" SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS -MINIMUM 3/8" SCALE.


SITE PLAN

1. INDICATE THE LOCATION OF GAS, WATER, SEWER OR SEPTIC LINES FROM THE STREET OR ALLEY TO WHERE THEY ENTER THE BUILDING. PROVIDE THE LOCATION OF YOUR WATER METER AND SEPTIC SYSTEM IF IT EXISTS.


FOUNDATION PLAN

1. NOTE ON THE DRAWINGS THE ALLOWABLE SOIL BEARING PRESSURE USED IN THE DESIGN OF THE FOOTINGS, OR STATE THAT THE ASSUMED VALUE OF 1,000 PSF IS BEING USED.

2. FOUNDATION DETAILS SHALL BE CROSS-REFERENCED TO THE FOUNDATION PLANS.

3. PROVIDE DIMENSIONS FOR SPACING OF POST FOOTINGS.


FLOOR PLAN

1. PROVIDE ALL WINDOW TYPES, AND DESIGNATE THE OPERABLE PORTION OF WINDOWS.

2. PROVIDE DIMENSIONS BETWEEN PORCH POSTS; ALSO A DIMENSION FROM THE HOUSE TO THE PORCH POSTS.




STRUCTURAL

1. SPECIFY LUMBER GRADE AND SPECIES / SPECIFY MANUFACTURER AND SERIES ON GLULAMS AND I JOISTS.

2. PROVIDE MANUFACTURERS CALCULATIONS AND DATA FOR PRE-FAB TRUSSES AND GLU-LAM BEAMS. TRUSS CALCS MUST BE SIGNED, DATED AND WET SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. TRUSS CALCS SHALL BE CROSS- REFERENCED TO THE ROOF FRAMING PLANS.

3. DOUBLE 2X8 HEADERS @ 6FT. OPENINGS ON NORTH & SOUTH SIDE APPEAR TO BE INADEQUATE. PROVIDE CALC'S OR USE LARGER LUMBER.

4. COMPLETELY DETAIL ALL CONNECTIONS AND CROSS REFERENCE TO THE FOUNDATION AND FRAMING PLANS:

- BEAM TO POST
- POST TO SLAB
- LEDGERS TO FRAME, FRAME TO LEDGERS
- JOIST TO LEDGER
- HANGER TYPES

5. REGARDING BRACED WALL PANELS. A MINIMUM PANEL WIDTH OF 48 INCHES IS REQUIRED UBC SEC 2326.11.3. TO EFFECTIVELY BRACE THE PARTITION.
IF BRACING DOES NOT COMPLY WITH UBC SEC 2326.11.3, PROVIDE A LATERAL ANALYSIS OR ALTERNATE DESIGN PER UBC 2326.11.4. A MINIMUM PANEL WIDTH OF 2'-8"WITH A HOLD DOWN DEVISE ON EACH END OF THE PANEL CAPABLE OF PROVIDING AN UPLIFT CAPACITY OF NOT LESS THAN 1,800 LBS. EACH. ALSO (2) ½"X 10"ANCHOR BOLTS AT QUARTER POINTS IN SILL PLATE. THE MAXIMUM HEIGHT OF THIS TYPE OF WALL IS 10 FT. THIS WILL BE REQUIRED AT THE EAST SIDE OF THE HOUSE AND GARAGE.

6. SPECIFY WEIGHT OF ROOF SYSTEM ITEMS...I.E. WEIGHT OF SELECTED TILE.
PROVIDE ICBO EVALUATION REPORT NUMBER AND MANUFACTURER OF ALL CONCRETE OR CLAY -TYPE TILE ROOFING.


ELEVATIONS

1. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH UBC SEC 1505.3. NOTE LOCATION OF ALL VENTS NEEDED TO COMPLY.

2. FOR THINCOAT STUCCO SYSTEMS OVER FOAM BOARD, NOTE AND SPECIFY THE ICBO EVALUATION REPORT NUMBER, SYSTEM NAME AND MANUFACTURER. NOTE AND SPECIFY THE VAPOR BARRIER.

3. CLARIFY NOTE ON SHEET #7 @ THE REAR ELEVATION. WHAT IS AIS SHEATHING IN LEIU OF FOAM. PROVIDE ICBO REPORT OR MANUFACTURES SPEC'S.





SECTIONS - DETAILS - MISCELLANEOUS NOTES

1. PROVIDE A BUILDING CROSS SECTION. MORE THAN ONE MAY BE REQUIRED TO CLEARLY ILLUSTRATE HOW THE STRUCTURE IS BUILT.

2. CROSS - SECTIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLAN AND FRAMING PLANS.


PLUMBING PLAN

1. PROVIDE AN ISOMETRIC DRAWING OF WASTE LINES.SHOW SIZES OF WASTE LINES, VENTS AND REQUIRED CLEANOUTS.

2 GAS: PROVIDE THE LENGTH OF LINE TO EACH APPLIANCE AND SIZE OF ALL PIPE .

3. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS AND SHOWER HEADS 3 GALLONS PER MINUTE. UPC CH.15 W/LOCAL MODIFICATIONS.

4. PROVIDE PRESSUE AND TEMPERATURE RELIEF VALVE AT WATERHEATER (UPC SEC. 608.3)

5. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE
INDIVIDUAL CONTROL VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE. PER. U.P.C. 410.7


MECHANICAL

1. SPECIFY THE SIZE OF AIR CONDITIONER.

2. SPECIFY THE LOCATION OF THE AIRHANDLER. IF THE HEATING OR AIR CONDITIONING EQUIPMENT IS LOCATED IN THE ATTIC, SHOW LOCATION OF ACCESS, CAT WALK, AND WORKING PLATFORM. SHOW PROVISIONS FOR AND ROUTE OF SECONDARY CONDENSE DRAIN. UMC SEC 319 & 310.


ELECTRICAL

1. NOTE ON PLANS THAT ALL ELECTRICAL WORK SHALL COMPLY WITH 1999 NEC.

2. PROVIDE AN EXTERIOR OUTLET AT GRADE LEVEL LOCATED AT BOTH THE FRONT AND THE BACK OF THE DWELLING. ( N.E.C. ART. 210-52(e).) THESE OUTLETS SHALL BE GFI PROTECTED. (N.E.C. ART. 210-8(a)(3).)

3. RECEPTACLE OUTLETS SHALL BE PROVIDED AT EACH KITCHEN COUNTER SPACE WIDER THAN 12 INCHES AND SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24 INCHES FROM A RECEPTACLE OUTLET. (N.E.C. ART. 210-52(c)(1).)
G.F.C.I. PROTECTION REQUIRED.

4. NOTE THAT LIGHT FIXTURES IN CLOTHES CLOSETS SHALL BE INSTALLED IN ACCORDANCE WITH (N.E.C. 410-8(d).)

5. NOTE THAT LIGHT FIXTURES IN TUB AND SHOWER AREAS SHALL BE INSTALLED IN ACCORDANCE WITH (N.E.C. 410-4(a)&(d).

6. NOTE THAT ALL SMOKE DETECTORS MUST HAVE A POWER SOURCE FROM THE BUILDING WIRING AND SHALL BE EQUIPPED WITH A BATTERY BACKUP.


MISCELLANEOUS

1. PROVIDE MODEL ENERGY CALCULATIONS.





IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WILLETT: 791-5550; EXT. 110
03/26/2001 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/28/2001 TAMI ACHONG OUT TO CUSTOMER Completed