Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T01CM01040
Parcel: 11803343A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T01CM01040
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2001 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T01CM01040
3/27/01 2ND REVIEW 5/17/01

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating the action taken.

GENERAL REQUIREMENTS:

1. All corrections and revisions shall be made on the original tracings. Return all redlined prints. The final package shall consist of two sets of drawings and related documents, one which the City shall retain and the other set will be stamped and returned to you.

2. To avoid delays, ensure all corrections have been made, are complete and have been coordinated on all applicable details and notes.

STRUCTURAL PLANS:

1. Specify and detail all overframing. If solid sheathing is used on the lower trusses, provide minimum openings of 22" by 30" for access and ventilation into overframed areas (> 30 s.f.). If solid sheathing is not used on lower trusses, provide details for bracing of top chord of lower trusses.

2. Indicate location of all masonry lintels.

ELECTRICAL PLANS:

1. A receptacle outlet shall be provided adjacent to the basin in each bathroom, per E3801.6. Bathroom outlets shall be on a separate 20-amp circuit with no other outlets, per E3603.4..

MODEL ENERGY CODE:

1. Call out on the plans the "R" values of insulation, as well as the "U" values of the windows and doors in conformance with the energy calculations provided.
DETAIL WALL INSULATION
TWO DIFFERENT SETS OF MEC CALCS HAVE BEEN PROVIDED--CLARIFY
MEC CALCS PROVIDED ARE USING WRONG VALUES FOR SEVERAL AREAS


IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS: @ 791-5550 EXT. 112
05/21/2001 GERRY KOZIOL WWM REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
05/22/2001 MONICA VALDEZ OUT TO CUSTOMER Completed