Permit Number: T01CM00874
Parcel: 140122180

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T01CM00874
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2001 JIM EGAN FIRE REVIEW Approved
02/22/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
02/22/2001 PETER MCLAUGHLIN ZONING REVIEW Approved
02/22/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
02/22/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved
02/26/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Approved
02/28/2001 GERRY KOZIOL WWM REVIEW Approved
02/28/2001 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied 1. CLARIFY WHERE 20% OF PROJECT VALUATION IS SPENT ON ACCESSIBILITY PER UBC SEC #1110 & 1112. 2. CLARIFY , ON DRAWINGS, MINIMUM OF 3 ACCESSIBILE CHECKOUT AISLES PER TABLE #11-E, SHOW COMPLIANCE WITH UBC, SEC #1106.24.3. 3. PROVIDE COMPLETE DETAILS FOR CONSTRUCTION OF WALL 02: INCLUDING CROSS-SECTION WITH MATERIAL OF CONSTRUCTION, AND CONNECTIONS TO STRUCTURE ABOVE AND BELOW WITH FASTENER TYPE , SIZE, SPACING /NUMBER.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/06/2001 TAMI ACHONG OUT TO CUSTOMER Completed