Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T01CM00874
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/22/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
02/22/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | |
02/22/2001 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
02/22/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
02/22/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
02/26/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
02/28/2001 | GERRY KOZIOL | WWM | REVIEW | Approved | |
02/28/2001 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | 1. CLARIFY WHERE 20% OF PROJECT VALUATION IS SPENT ON ACCESSIBILITY PER UBC SEC #1110 & 1112. 2. CLARIFY , ON DRAWINGS, MINIMUM OF 3 ACCESSIBILE CHECKOUT AISLES PER TABLE #11-E, SHOW COMPLIANCE WITH UBC, SEC #1106.24.3. 3. PROVIDE COMPLETE DETAILS FOR CONSTRUCTION OF WALL 02: INCLUDING CROSS-SECTION WITH MATERIAL OF CONSTRUCTION, AND CONNECTIONS TO STRUCTURE ABOVE AND BELOW WITH FASTENER TYPE , SIZE, SPACING /NUMBER. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/06/2001 | TAMI ACHONG | OUT TO CUSTOMER | Completed |