Permit Number: T01CM00827
Parcel: 129011040

Address:
2110 E 19TH ST

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T01CM00827
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2001 JIM EGAN FIRE REVIEW Denied FIRE SPRINKLERS REQUIRED.
06/05/2001 TOM CLARK WATER REVIEW Passed
06/18/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Denied
07/13/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E-1
1) Please clarify what the existing building (housing the new saw) is used for? What type of saw is it and what will it be used for?
E-2
1) Provide the starter size for the E.C's. It appears it should be a size 0 minimum.
2) There is an 80% difference between phase A and phase C on panel N. Thus the high phase current must be used in the panel and load analysis.
3) Provide fault current at service POA. Provide fault current analysis for panels T and A.
4) Provide a WP/GFCI receptacle on the roof within 25' of E.C.'s. 99NEC 210-8, and 210-63
5) There is a receptacle on the exterior of the building without a circuit number.
E-3
1) Please provide a fixture cut for fixture B.
2) The IECC will only allow .6 watts/ft2. In addition you must provide dual
switching which will approximate a uniform 50% reduction of the lighting load. See IECC 705.
07/16/2001 BOB SUBA PLUMBING-COMMERCIAL REVIEW Approved
07/16/2001 BOB SUBA MECHANICAL-COMMERCIAL REVIEW Approved
07/18/2001 PHIL SEADER BUILDING-COMMERCIAL REVIEW Denied
07/23/2001 MICHAEL ST. PAUL ZONING REVIEW Denied
07/23/2001 GERRY KOZIOL WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/09/2001 SUE REEVES OUT TO CUSTOMER Completed