Review Details: COMMERCIAL TI
Permit Number - T01CM00708
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/14/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
| 02/14/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 02/15/2001 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 02/26/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. Cleanouts are required at P03, P21 and P31. Note: P31 is indicated as E31 on P1.1 and P4.0-- change. 2. Provide the total length of gas line on the plan. 3. The expansion tank should be down stream of the shut off valve on the C.W. side of the W.H. 4. All plumbing fixtures shall have a Recognized listing on them. Note: A Mechanical Engineer should seal the plans. |
| 02/26/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Return air does not comply with Sec 317.3.2, 317.3.3, and 317.3.4 UMC1994. 2. Smoke detector does not comply with Sec 608 UMC1994. 3. Dryer Exaust vet does not comply with Sec 504.3.1 UMC1994. Have a registered Mechanical Engineer Seal the plans. |
| 02/27/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | E1.0 1) Provide a minimum of #10 wire for circuits A-12, 14 and A-4. E2.0 1) Provide the VA (not wattage) rating for fixture type L16. The loads in the panel appear to reflect approximately 17 VA per fixture. E3.2 1) Provide the service capacity and total service load. GENERAL COMMENTS Please return the plans I have already reviewed along with your next submittal. |
| 03/12/2001 | MVALDEZ | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 03/12/2001 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/16/2001 | GERRY KOZIOL | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/16/2001 | DELMA ROBEY | OUT TO CUSTOMER | Completed |