Permit Number: T01CM00708
Parcel: 11205283F

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T01CM00708
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
02/14/2001 JIM EGAN FIRE REVIEW Approved
02/15/2001 PETER MCLAUGHLIN ZONING REVIEW Approved
02/26/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Return air does not comply with Sec 317.3.2, 317.3.3, and 317.3.4 UMC1994. 2. Smoke detector does not comply with Sec 608 UMC1994. 3. Dryer Exaust vet does not comply with Sec 504.3.1 UMC1994. Have a registered Mechanical Engineer Seal the plans.
02/26/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Cleanouts are required at P03, P21 and P31. Note: P31 is indicated as E31 on P1.1 and P4.0-- change. 2. Provide the total length of gas line on the plan. 3. The expansion tank should be down stream of the shut off valve on the C.W. side of the W.H. 4. All plumbing fixtures shall have a Recognized listing on them. Note: A Mechanical Engineer should seal the plans.
02/27/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E1.0
1) Provide a minimum of #10 wire for circuits A-12, 14 and A-4.

E2.0
1) Provide the VA (not wattage) rating for fixture type L16. The loads in the panel appear to reflect approximately 17 VA per fixture.

E3.2
1) Provide the service capacity and total service load.

GENERAL COMMENTS
Please return the plans I have already reviewed along with your next submittal.
03/12/2001 MVALDEZ BUILDING-COMMERCIAL REVIEW Completed
03/12/2001 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
03/16/2001 GERRY KOZIOL WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/16/2001 DELMA ROBEY OUT TO CUSTOMER Completed