Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T01CM00657
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/12/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
| 04/18/2001 | PETER MCLAUGHLIN | ZONING | REVIEW | Denied | |
| 05/15/2001 | INGA DAVIDSON | WATER | REVIEW | Approved | |
| 05/16/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Model Energy Code calculations are not with plan set. 2. Provide access to the mechanical equipment on the roof per Sec 306.5 IMC 2000. |
| 05/16/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. Provide the UP and DOWN stream M.H. Rim Elev., Inverts on sheet SP1.0. 2. 2. Evaporative cooler drain can not discharge onto asphalt. NOTE: SP1.0 ( no landscaping) Sec 307.2.1 IMC 2000. |
| 05/17/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1) The electrical service cannot protrude into the alley. 2) Please include an OH service waiver in your next submission. 3) Please provide a fault current statement. |
| 05/22/2001 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 05/23/2001 | ESTEVAN TINEO | FLOODPLAIN | REVIEW | Denied | The project needs a Floodplain Use Permit from DOT Floodplain. |
| 06/01/2001 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/25/2001 | SUE REEVES | OUT TO CUSTOMER | Completed |