Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T01CM00654
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/13/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | E-01 1) Carry the 1/0 equipment ground from the 400 amp fused switch to the transformer and bond to the transformer enclosure. In addition include a grounding electrode system in the 400 amp fused switch, connect it to the grounded conductor (neutral) of the service lateral and bond both to the 400 amp fused switch enclosure. The secondary feeder of the 100 kVA transformer serving the 400 amp circuit breaker should not include an equipment ground. Do not bond the neutral to ground in the transformer. Bond the neutral to the grounding electrode system in the 400 amp circuit breaker and bond both to the switch enclosure. This grounding scheme will prevent the possibility of normal neutral currents on the equipment grounding conductors. See originally submitted blue line documents, I have redlined the requirements on the plan. See 99NEC 250-30 2) Circuit A-31 on page E-04 serves 12 receptacles at 180VA each, therefore the load in the panel on page E-01 should be 2160VA minimum. In addition the total load exceeds the rating of the 15 amp circuit breaker. See 99NEC 220-3(b)(9). 3) It appears the circuit breakers serving the AC's should be reduced to 50 amps. GENERAL COMMENTS 1) Provide a disconnect within site of each of the AC's or provide a circuit breaker capable of being locked in the open (off) position. See 99NEC 440-14 ex 1 2) Please return the blue line plans I have already reviewed along with your next submission. |
| 02/14/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/27/2001 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE FIRE-RATED CONSTRUCTION DETAILS CONFORMING TO LISTING USED TO JUSTIFY FIRE RATING AT EXTERIOR WALLS, REF 2/A-05, PROVIDE COMPLETE FIRE-RATED DETAILS AT: 1. DOOR FRAME ( JAMB AND HEAD), 2. WALLS AT ( FOUNDATION, CEILING, STRUCTURE ABOVE, NEW WALLS TO EXISTING WALLS, PENETRATONS,etc.),3. ACCESS LATCH DETAILS A/A-06 AT REPAIR AND NEW LOCATION. 2. PROVIDE LANDING AT EACH SIDE OF DOOR AT STAIR PER UBC SEC #1006.7. 3. PROVIDE DETAIL FOR SUPPORT OF CABLE TRAY ON EXTERIOR METAL STUD WALL, REF 2/E-06. 4. SPECIAL INSPECTION PER SOILS REPORT. |
| 02/27/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/05/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 03/13/2001 | JAY HOGAN | OPERATIONS | REVIEW | Approved | |
| 03/13/2001 | GLENN MOYER | PLANNING-CITY HALL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/06/2001 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 03/14/2001 | DELMA ROBEY | REJECT SHELF | Completed |