Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T01CM00610
Parcel: 12901044C

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T01CM00610
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
02/08/2001 JIM EGAN FIRE REVIEW Approved
02/09/2001 MARK TITUS WATER REVIEW Approved
02/14/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Model energy code calculations have some incorrect numbers for the wall area and U-Value given for same. 2. Show on the plan where AC-4 condensate runs.
02/14/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Provide the waste fixture units at each branch on the isometric drawings. 2. Provide the manufactures name , listing, etc. Per Sec301.1.1,301.1.2, and 301.1.3UPC1994. 3. Provide the manufactures name for the pressure type vac breaker- Detail 8 on P1.4. 4. Provide a backflow prevention device on the Panwasher Detail 18 on P1.4 and one on the 3-comp sink Detail 19 on P1.4.
02/16/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E0.2
1) Provide the fixture cuts including catalog numbers for the parking lot lights.
2) The equipment ground serving the lights and signs must be increased to a #8 copper. Reference 99NEC 250-122(b)
3) Circuit L3-42 serves the irrigation controller however it is not in the panel.
E1.1
1) Remove the equipment ground from the service lateral. Reference 99NEC 250-30(a)(1)ex1, 32(b)1 in principle, 310-4, and 347-4ex3
2) Conductor lengths for fault calculations are incorrect. See cable lengths for F6, F7, F8, F9, F10, F11, and F12. As a result the fault levels are higher than calculated and the panels are not properly braced.
3) The refrigeration panel must be rated 75,100 amps when protected by the fuses specified. Please note this series rating requirement on the plan. See keynote 18. See 99NEC 90-7,110-3(a)(b), 110-9, 110-10, 110-22, 240-86(a)(b).
4) The main bonding jumper keyed note 4 must be a minimum of 600kcmil. Reference 99NEC 250-28(d).
5) Keynote 19 should reference 99NEC 250-104(d). Keynote 3 should reference 99NEC 250-104.
6) Although the # 4 ufer grounding electrode meets code requirements it appears to me that perhaps a larger conductor should be utilized. I realize that in a ground fault the majority of the current will be carried by the neutral back to the transformer. However given the fact that we live in an area prone to lightning strikes it would seem prudent to prepare for a strike that could reach a magnitude of a 110kA.
E2.2 AND E3.5
1) Detail 7 and 9 indicate 12" slack wires which is incorrect. In addition the reference to the UBC is incorrect. Reference the 99NEC 410-16 (c) as amended by the City of Tucson.
E3.1
1) Panel BK appears to be mounted over a shelf. Col F6-F8. Reference 99NEC 110-26
2) The duct configuration described at column E6 does not match detail 4 on page E3.3.

Page 2 of 3

3) Add a note to the plan to read "PROVIDE A DISCONNECT FOR ALL APPLIANCES IN ACCORDANCE WITH 99NEC 422 PART C."
4) Circuit R2-6 serves bath receptacles on column E3 through F3 however the circuit is not in the panel.
5) Keynote 31 on column C7 through C10 appears incorrect. The circuit serves roll up gates. One line keynote 18 which serves
6) Add a note to the plan to read "PROVIDE A DISCONNECT WITH FUSES SIZED IN ACCORDANCE WITH THE MANUFACTURER WITHIN SIGHT OF EVERY MOTOR CONTROLLER. IF THE MOTOR IS NOT WITHIN SIGHT OF THE MOTOR THE DISCONNECT SHALL BE LOCKABLE IN THE OPEN (OFF) POSITION."
7) There are a number of 3 phase 208 volt pieces of equipment circuited to panel MA in the meat area. See column B to C, 10 to 114. Provide overload protection and horsepower rated disconnects in accordance with 99NEC 430. In addition MA 1,3,5 page E4.1 is served by a 35 amp circuit breaker however no wire size is specified. Provide 99NEC article 400 justification for cord drop and receptacle connections for what appears to be fixed (not portable) equipment.
E3.1.1
1) Provide fused disconnects for TF1 on column F16, EF6 on column F2, Deli box fan coil on column F1, and TF2 on column C2. As an option you may reduce the circuit breakers to 15 amp in the panels and provide motor bulletin switches with overload heaters. Reference 99 NEC 430 part C and J
2) Circuit CF1-20 on column C14 appears to be incorrect perhaps it should be circuit 40.
3) Circuit R3-26,28,30 serving AC-3 is incorrect, perhaps it should be DA-26,28,30
4) Provide a fused disconnect for FF1 on column A7. See 99NEC 430 Part C, E, and J.
5) Circuit R1-7 does not serve the hot water tank on column C5.
6) The 20 amp circuit breaker (CF2-5) serving fans in the Dairy Case must be reduced to 15 amp in order to provide proper short circuit protection. See 99NEC 430 Part E
7) Provide a fused disconnect for AC4 on column A7 or comply with 99NEC 440 Part G.
8) Provide a fused disconnect for UH1 on column A5. See 99NEC 430 Part C, E, and J.
9) Provide a circuit and fused disconnect for EF-12 or provide a Motor Bulletin switch and a 15 amp circuit breaker. See column B5 to C5. See 99NEC 430 Part C, E, and J.
Page 3 of 3

E3.1.3
1) Both panels XL and SL2 lack proper work clearance. See the Control Room Detail. See 99NEC 110-26
2) Add a note on page" ALL APPLIANCES SHALL BE PROVIDED WITH A DISCONNECT CONFORMING TO 99NEC 422 PART C."

GENERAL COMMENTS
1) Please return the plans I have originally reviewed upon your next submission. I must have them prior to commencing my next review.
04/16/2001 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE DOCUMENTS WITH MINIMUM OF 10 POINT FONT, DRAWINGS, CALCS, SPECS... 2) PROVIDE SOILS REPORT TO A DEPTH OF 30 FEET MINIMUM PER ATTACHED MEMORANDUM DATED JULY 7,1986 . 3) CLARIFY PREMISES IDENTIFICATION ON NORTH ELEVATION DRAWING A2.1 PER UBC SEC. #502. 4) PROVIDE ADDRESS PER PIMA COUNTY ADDRESSING ORDINANCE, SEE ATTACHED EXCERPT. 5) DEMOLITION PERMIT/S REQUIRED FOR OTHER STRUCTURE/S ON THIS SITE PRIOR TO ISSUANCE OF THIS PERMIT. 6) PROVIDE 10 POINT FONT MINIMUM ON DRAWING T0.2. 7) PROVIDE CONSTRUCTION DETAILS ON DRAWINGS FOR FIRE-RATED CONSTRUCTION CONFORMING TO LISTING OF FIRE-RATED ASSEMBLIES. 8) PROVIDE LISTINGS ON THE DRAWINGS FOR FIRE-RATED ASSEMBLIES, INCLUDING JOINTS, CAULKING, SHAFTS,WALLS,ROOF, PENETRATIONS, ETC.. 9) REVISE DETAIL 18/A2.4 TO PROVIDE 10 POINT FONT MINIMUM. 10) SUBMIT TWO SETS OF SHOP DRAWINGS FOR EXIT DOORS, PER STAMP. 11) STORAGE RACKS OVER 8 FEET RQUIRE A BUILDING PERMIT. 12) CLARIFY SITE GRADING CONFORMANCE TO UBC SEC. # 1106.8.6, EXTERIOR RAMPS.." SHALL BE CONSTRUCTED TO PREVENT THE ACCUMULATION OF WATER ON WALKING SURFACE." ie: S.W. RAMP ADJACENT TO LOADING BAY REF. DWG. C1.4. 13) SUBMIT TWO SETS OF SHOP DRAWINGS FOR: 1.RAMP HANDRAILS 2.STAIR HANDRAILS 3.STEEL ROOF DECKING 4.STEEL ROOF JOISTS 5.STEEL ROOF GIRDERS 6.SATELLITE DISH . 14) CLARIFY DETECTABLE WARNINGS PER UBC SEC.#1106.4.5.2 AND #1106.17, ON DRAWINGS. 15) CLARIFY EDGE PROTECTION AT RAMPS, PER UBC SEC.#1106.8.7, SHOW ON DRAWINGS. 16) CLARIFY RAMP/EXIT DOOR RELATIONSHIPS AT DOOR/S #06 AND #22, ie: MOVE/ DIMENSION RAMP/LANDING TO SOUTH TO ALLOW SOUTH LEAF OF DOOR TO OPEN FULLY 180 DEGREES AND CLEAR TOP OF HANDRAIL, PER UBC CHAP #11, AS AMENDED,AND CHAP #10, SEC #1004.10, SEC#1007.4. 17) CLARIFY DOOR SWING/ LANDING / STAIR AT DOOR #13, MAYBE SWING DOOR THE OTHER WAY, AWAY FROM STAIR. 18) CLARIFY NUMBER , ACCESSIBILITY AND LOCATION OF REQUIRED ACCESSIBLE CHECKOUT AISLES PER UBC CHAPTER #11,AS AMENDED, TABLE #11.E, SEC #1106.24.3 AND #1106.20. 19) CLARIFY EIFS COMPATABILITY AND CONFORMANCE TO THE CONSTRUCTION TYPE, OCCUPANCY AND MATERIALS OF THIS BUILDING, PROVIDE ICBO EVALUATION REPORT NUMBER OF STUCCO/ INSULATION SYSTEM ON THE DRAWINGS, UBC SEC #25 AND 26. 20) CLARIFY CODE COMPLIANCE OF ' EQUIPMENT ROOM', 11' x 48' BUILDING ADJACENT TO THE STORE BUILDING, TYPE OF CONSTRUCTION, LOCATION ON PROPERTY, EXTERIOR WALL PROTECTION, ETC.. 21) PROVIDE COMPLETE DESIGN OF "KNIFE PLATE" CONNECTION, INCLUDING STIFFENERS REQUIRED AND WELDING, REF 4/S3.2, 23/S3.2, 31/S3.2, CALC'S PG 34,34A, 34B,AND 34C, ETC.. 22) WHERE ARE ADDITIONAL JOIST LOADS CALLED-OUT ON CALC PG 44C NOTED ON DRAWINGS? 23) PROVIDE COMPLETE LATERAL ANALYSIS " BY INSPECTION " IS NOT ACCEPTABLE FOR A BUILDING OF THIS SIZE AND SEISMIC APPEARS TO GOVERN IN E-W DIRECTION AND IS VERY CLOSE IN N-S DIRECTION. 24) PROVIDE STRUCTURAL CALCULATIONS AND DETAILS FOR SEISMIC ANCHORAGE OF EQUIPMENT AND NON-STRUCTURAL ELEMENTS SUPPORTED BY STRUCTURE PER UBC SEC #1630. 25) PROVIDE COPIES OF INSPECTION PROGRAM PER UAC SEC #302.5. 26) SPECIAL INSPECTION REQUIRED AS NOTED FOR : 1. SITE PREPARATION OF THE BUILDING PAD 2. FOUNDATION EXCAVATION AND COMPACTION 3. SPRAYED ON FIREPROOFING 4. STRUCTURAL MASONRY 5. FIELD WELDING 6. CONCRETE 7. BOLTS IN CONCRETE 8. REINFORCING 9. EPOXY ANCHORS 10. MASONRY WALL BRACING SYSTEM , ie: BOND BEAMS, CONNECTIONS, BRACING,AND EMBEDMENTS.
05/07/2001 DAN CASTRO ZONING REVIEW Denied
05/07/2001 GERRY KOZIOL WWM REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
08/08/2001 DELMA ROBEY OUT TO CUSTOMER Completed