Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T01CM00610
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/10/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/10/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 08/15/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/26/2001 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | ......T01CM00610........1940 E BROADWAY.......DGL....9/29/01...... SECOND REVIEW COMMENTS...................................................... 1. SEE PRIOR COMMENT #7 . PROVIDE REQUESTED FIRE-RATED CONSTRUCTION DETAILS ON THE DRAWINGS. 2. SEE PRIOR COMMENT #20. . .................................................... 3. SEE PRIOR COMMENT #25. INSPECTION PROGRAM IS INCOMPLETE. PROVIDE AN INSPECTION PROGRAM FOR ALL LISTED SPECIAL INSPECTIONS ( SEE COMMENT #26 ) WITH NO REVISIONS OR ELIMINATIONS. PROVIDE ALL INFORMATION REQUIRED BY 1994 UNIFORM ADMINISTRATIVE CODE SECTION 302.5, SEE ATTACHMENT. ATTACHMENTS ARE WITH HARD COPY ATTACHED TO SUBMITTAL DOCUMENTS, THESE INCLUDE PRIOR COMMENTS W/ ATTACHMENTS AND EXCERPT FROM 1994 UAC SEC 302.5. |
| 11/01/2001 | GERRY KOZIOL | WWM | REVIEW | Denied | |
| 11/01/2001 | JKOZUCH | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/09/2001 | DELMA ROBEY | OUT TO CUSTOMER | Completed |