Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Permit Number - T01CM00476
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/30/2001 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 01/30/2001 | DWILLIAM | NPPO | REVIEW | Passed | PASSED BY j. lINVILLE n/a |
| 01/30/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 03/02/2001 | DAVE WILLETT | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T01CM00476 03/02/01 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESUBMIT TWO SETS OF CORRECTED PLANS. SUBMIT A COPY OF THIS LETTER , NOTING THE DETAIL AND OR SHEET WHERE THE CORRECTION MAY BE FOUND. GENERAL REQUIREMENTS 1. PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. FLOOR PLAN 1. SHOW COMPLIANCE WITH UBC SEC 1203.2 & 3 PROVIDING NATURAL LIGHT AND VENTALATION INTO THE BASEMENT AREA. 2. SHOW COMPLIANCE WITH UBC SEC 310.4, PROVIDING EGRESS FROM BASEMENT. 3. DETAIL AND SPECIFY STAIR WIDTH, RISE AND RUN, LANDING WIDTH, HANDRAIL HEIGHTS, GUARDRAIL HEIGHT AND INTERMEDIATE RAIL SPACING. PER UBC SEC 1006 AND SEC 509. PROVIDE STAIRWAY CONNECTION DETAILS AND STRINGER SIZES. STRUCTURAL 1. PROVIDE (IN ENGINEERS CALC'S AND ON PLANS) THE TYPE, SIZE AND METHOD OF ATTACHMENT OF HEADERS THAT SUPPORT THE RAFTERS AND FLOOR JOISTS AT THE FIRE PLACE'S IN THE MASTER BED ROOM, KITCHEN AND FAMILY ROOM. 2. FIRE PLACE CHIMNEY NOT TO SUPPORT OTHER LOADS. PER UBC 3102.3.1. I.E. PORCH ROOF LOADS. SUBMIT CALC'S FOR ADDITIONAL LOADS. ALSO ADDRESS THE 2" MIN. CLEARANCE TO COMBUSTIBLES. I.E. PORCH RAFTERS. 3. DOUBLE FIRE PLACE FLUES ARE TO BE DIVIDED BY CMU. PER UBC 3102.4.6 4. PROVIDE SPECIAL INSPECTION FORMS FOR WELDING PER GSN SHEET AND ADHESIVE ANCHOR BOLTS PER 3/S1. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WILLETT: 791-5550; EXT. 110 |
| 03/08/2001 | GERRY KOZIOL | WWM | REVIEW | Denied |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/22/2001 | DELMA ROBEY | OUT TO CUSTOMER | Completed |