Permit Number: T01CM00462
Parcel: 137051210

Address:
4902 S 12TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T01CM00462
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2001 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1) SEE PRIOR COMMENT # S2). CLARIFY ACCESSIBILITY ,PER 1994 UBC CHAPTER 11 AS AMENDED, REQUIRES 20 % OF VALUE OF PROJECT TO BE SPENT ON ACCESSIBILITY FOR "PATH OF TRAVEL" AS DEFINED IN SEC. 1110 AND 1112- THIS DEFINITION INCLUDES SITE, PARKING, ACCESS TO PUBLIC WAY, ACCESS TO THE BUI8LDING AS WELL AS WITHIN THE BUILDING , EXPLAIN/SHOW HOW YOUR DESIGN COMPLIES S2) SEE PRIOR COMMENT #S5). SHOW FASTENER : TYPE, SIZE SPACING/NUMBER AT CONNECTIONS OF WALLS TO STRUCTURE ABOVE AND BELOW.
03/08/2001 PETER MCLAUGHLIN ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/08/2001 MVALDEZ OUT TO CUSTOMER Completed