Permit Number: T01CM00360
Parcel: 13313005E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T01CM00360
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2001 DAVID RIVERA ZONING REVIEW Approved
01/23/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
01/24/2001 JIM EGAN FIRE REVIEW Approved
01/25/2001 PHIL SEADER BUILDING-COMMERCIAL REVIEW Approved
02/01/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied
02/05/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied See comments under Mechanical.
02/05/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the manufactures name, listing, design pressure, type and schedule and installation standards for the CNG lines. Put on the plans. 2. Move the Purge Air Line from the side of the Island ( Sec B P2.2 to the North side of the column. Physical damage could happen with it exposed on the side of the island. Provide calculations showing Expansibility in the 4 inch PVC pipe. Provide an expanable joint at the dispenser. 4. Vent the 4 incn PVC pipe at the compressor area with a Tee and a 90 degree elbow, with a insect screen. TAKE NOTE: Pressure Safety Valve ( Relief Valve) shall comply with A.S.M.E. Rules. Shut-OFF valve ( Supplied w/tank) ( Isolation Valve) Shall be ALARMED.
02/07/2001 TGRIFFUS WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/12/2001 DELMA ROBEY OUT TO CUSTOMER Completed
02/12/2001 DELMA ROBEY APPROVAL SHELF Completed
02/07/2001 DELMA ROBEY REJECT SHELF Completed