Permit Number: T01CM00353
Parcel: 133231610

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T01CM00353
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2001 DAVID RIVERA ZONING REVIEW Approved
01/23/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
01/24/2001 JIM EGAN FIRE REVIEW Approved
01/29/2001 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied
01/30/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. An expansion tank is required on the C.W. side of the W.H. down stream of the S.O.V. Sec608.3 par 3 UPOC1994 2. Provide a C.O. at the S2 per Sec 707.0 UPC1994 3. 3. Comply with Sec710.0UPC1994 on the sump pump Detail 2 on MPL-1, complete this isometric, Show how it connects to existing waste.
01/30/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied MECHANICAL 1. The architect of record shall provide a complete detail of the One Hour chase required for the Type-I hood. This shall inclued the construction, support of the chase and hood to the structure.
01/30/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Provide make-up air per Sec 402.4UMC1994
02/01/2001 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied
02/02/2001 TGRIFFUS WWM REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
02/15/2001 DELMA ROBEY OUT TO CUSTOMER Completed