Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T01CM00353
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/23/2001 | DAVID RIVERA | ZONING | REVIEW | Approved | |
01/23/2001 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
01/24/2001 | JIM EGAN | FIRE | REVIEW | Approved | |
01/29/2001 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | |
01/30/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. An expansion tank is required on the C.W. side of the W.H. down stream of the S.O.V. Sec608.3 par 3 UPOC1994 2. Provide a C.O. at the S2 per Sec 707.0 UPC1994 3. 3. Comply with Sec710.0UPC1994 on the sump pump Detail 2 on MPL-1, complete this isometric, Show how it connects to existing waste. |
01/30/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | MECHANICAL 1. The architect of record shall provide a complete detail of the One Hour chase required for the Type-I hood. This shall inclued the construction, support of the chase and hood to the structure. |
01/30/2001 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide make-up air per Sec 402.4UMC1994 |
02/01/2001 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | |
02/02/2001 | TGRIFFUS | WWM | REVIEW | Denied |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/15/2001 | DELMA ROBEY | OUT TO CUSTOMER | Completed |