Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T01CM00202
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/28/2003 | GP | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | ARCHITECTURAL COMMENTS General 1. Please provide a specification, listed by an approved testing agency, for the protection of penetrations to horizontal assemblies. Ref. IBC 711.4. PLUMBING COMMENTS General 1. Please specify the slope of the horizontal drainage piping. Ref. UPC 708. 2. Note 2, providing contact information for material specification, does not appear to apply. Please clarify. ELECTRICAL COMMENTS Sheet 3E4.1 1. The service information shown in the ejector schedule on Sheet 3P4.4 does not agree with the load summary notes. Please coordinate and clarify. |
| 07/28/2003 | EROSE1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/28/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |