Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T01CM00171
Parcel: 122131000

Review Status: Completed

Review Details: SITE

Permit Number - T01CM00171
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2001 JIM EGAN FIRE REVIEW Approved
01/24/2001 DAN CASTRO ZONING REVIEW Denied
01/26/2001 JOE LINVILLE NPPO REVIEW Denied
01/26/2001 JLINVILL LANDSCAPE REVIEW Denied
02/12/2001 TOM WEIDEMAN FLOODPLAIN REVIEW Denied See engineering comments
02/12/2001 TOM WEIDEMAN ENGINEERING REVIEW Denied Site Plan Comments

1. The 24' PAAL opening should be located a minimum of six west of the east property line.
2. Show and call out adjacent driveway openings next to this development. Provide distances from existing openings to proposed openings.
3. Move the near side sight visibility triangle west to the edge of the proposed driveway opening.
4. Relocate the southerly most refuse collection area so the refuse collection vehicle will not be backing into the crosswalk area to turn around.
5. Call out the drainage structure and wall openings at the southerly end of the PAAL.
6. The Q100 CFS of 1.22 shown at the southerly end of the development appears to be incorrect per the drainage statement. Please make the appropriate corrections.
7. Provide estimated cut and fill quantities.
8. Provide a description of the basis of elevation including the COT field book and page number.

Drainage Statement Comments

1. The description of the offsite drainage on page two beginning with the fifth paragraph " The runoff from the offsite basin…" is not consistent with what is being shown on the plans or page eight of the drainage statement.
2. Describe and show all onsite drainage per section 2.3.1.3.B of the Standards Manual for Drainage Design and Floodplain Management.
3. On page nine please show only the equation that was used to rate the scupper.
4. The center building FFE is inconsistent with what is shown in the drainage statement.
02/12/2001 PHIL SEADER HANDICAP-SITE REVIEW Approved
02/12/2001 TOM WEIDEMAN SANITATION REVIEW Denied see engineering comments

Final Status

Task End Date Reviewer's Name Type of Review Description
03/28/2001 MVALDEZ OUT TO CUSTOMER Completed